| 1 |
The panel over all dimensions W=600MM, D=800mm, HT=2250mm, Dimension for DCDB W=600mm and HT=2250mm D=800mm |
| 2 |
The battery charger will have the fine fibre type washable filler at the bottom. |
| 3 |
Two ventilating Fan- 6" on the top of the panel with canopy on charger. |
| 4 |
All the connection from DCDB will be on the back side of the panel The MCB's SFU will be seen from Rear side of DCDB. |
| 5 |
The charger panel + DCDB with single front as shown in the cabinet Drawing There will be mother door opening only for DCDB at Rear side, The SFU, MCB's will be operated from the Rear side after opening the door DCDB. |
| 6 |
Charger with DCDB 100 Amp ; 60 Amp |
| 7 |
All meters ACV, DCV, DC-1 - 96*96 size ; Make - Zeal |
| 8 |
For inter connecting cabling and routing PVC channel: Rated type of Lugs, PRC Connector will be need. |
| 9 |
Minimum 300mm clearance from bottom of the panel will be kept for working. |
| 10 |
All the component like Transformer, capacitor, in direction, meter's etc will not be shared with DCDB. |
| 11 |
FCBC charger will be with single door; A vertical separator internal will be provided between, FCBC & DCDB |