| 1. |
Technology |
: |
USING IGBT Technology |
| 2. |
Switching Frequency |
: |
High Frequency to ensure -
* Low Switching Lossess
* Purity of Sine-Wave * Very Low Noise
|
| 3. |
Wide Input Range |
: |
* 350 V - 475 V AC (Three phase)
* 45 - 60 Hz |
| 4. |
Accurate Output |
: |
* 415 v AC 1.0% (Three Phase)
50 Hz + 0.1 % (Crystal Controlled) |
| 5. |
Ratings |
: |
5.0 - 60.0 KVA |
| 6. |
O/P Power Factor |
: |
0.8 lagging to unity |
| 7. |
Metering |
|
LED Panel meter to display following Parameters
(Optional): |
|
|
|
: |
* Output Voltage *
Input Voltage
* Battery Voltage *
Input Frequency
* Output Frequency * Various
conditions/Parameter of UPS Power etc. OR
* Digital Meter showing Input/Output Volts through selection.
(STANDARD FEATURE) |
| 8. |
Overload Rating |
: |
100 % Continuous 150% for 30 seconds |
| 9. |
Operating Temperature |
: |
0 to 50o C, 95% R.H. (Maximum) |
| 10. |
Inverter Efficiency |
: |
* Better than 90% |
| 11. |
Genset Compatibility |
: |
* UPS System is fully Compatible to
any type of Genset |
| 12. |
Protections |
: |
* Output Over-Voltage
* Output Overload.
* Output Short Circuit
* Battery Under-Voltage
* Forced Air-cooling |
| 13. |
Indications |
: |
* Mains/Charger ON
* Inverter ON
* System Over-load
* Battery Under-Voltage
* Output Under/Over Voltage |
| 14. |
Alarms |
: |
* Mains Fail & Battery Low Warning
(Musical Alarm) |
| 15. |
Low Noise |
: |
Less than or Equal to 45 dB (A)
(Standard) at 1.0mtr. |
| 16. |
Battery Charger |
: |
* Charger is designed on Boost/Trickle (CCCV)
principle to keep batteries in top condition.
* Uses High Frequency design to ensure long battery life. |
| 17. |
Mobile Connectivity |
: |
Provided (Optional) |