The battery charger is serving the twin purpose
of supplying the DC load and simultaneously charging 70 AH, 110
Volts SMF lead acid batteries.
|
I
|
Input |
|
|
II
|
Rated operating Voltage
Limiting operating Voltage
Limiting operating current |
3 Phase, 415 Volts 5%
3 Phase, 415 Volts 15%
20 Amp |
|
III
|
Output
i) Rated output Voltage
ii) Battery charging current
iii) Maximum Output Current
iv) Maximum load current
v) Maximum output power |
Function of (Battery voltage, battery current, temperature
of the battery)< 135 V
20 Amps
50 Amps
50 Amp minus battery charging current
130 VX50 Amp = 6500 watts |
|
IV
|
Ripple Current |
V<3V; i<2 Amp |
|
V
|
Degree of protection |
IP52 as per IEC 529 |
|
VI
|
Interface |
Display of fault memory for diagnostic and subsequent
analysis of fault on PC through RS-232 |