| Parameters (7.5 KVA - 150 KVA) |
| Input |
| Voltage Range |
: |
415V +20% -30% |
|
|
| Output |
|
| Frequency |
: |
50Hz +/- 0.1% |
|
| Transient Response |
: |
+/- 5%,recovers within 5mSec (100% load variation) |
|
|
| Overload Capacity |
: |
120% load 30 seconds |
|
|
| Technology |
| Design |
: |
PWM, Double conversion |
|
|
| Compatibility |
: |
All gensets |
|
| Operating Temperature |
: |
10 C to 50 C / 0 to 95 % RH |
|
| |
| Battery |
| Voltage |
: |
240V/324V/360V/384V |
|
| Charger |
: |
CCCV, Float/Boost/Extended |
|
| Efficiency |
|
| Transfer time |
|
| Protection |
| Battery |
: |
Battery Under Voltage |
|
| Overload |
: |
Output Overload |
|
| Short Circuit |
: |
Current Limited and cut-off and fuse and breaker |
|
|
| EMI / EMC |
: |
EN50091-2, CE Approved |
|
|
| Environment |
| Relative Humidity |
: |
20-90% non-condensing |
|
| Audible noise |
: |
< 45 dB at 1mt length ( above ambient ) |
|
| Optional |
| Shut Down Software |
Load monitoring |
Battery Monitoring |
| Remote Control |
SNMP |
LCD/LED panel |
|